Ei Electronics Ei407

Ei Electronics Ei407 manual

(1)
  • 1. INTRODUCTION
    Pressing on the Ei407 Manual Call Point (MCP) black spot causes all
    Alarms on RadioLINK Bases and RadioLINK Alarms to sound. This
    informs the occupants that the building must be evacuated.
    The Ei407 MCP also provides a means to test the Alarms without
    having to reach up to the Alarms on the ceilings, as it can be reset
    with the plastic key (supplied).
    We suggest that the plastic key is mounted on a small nail under or
    alongside the MCP for future use when resetting (as shown above).
    2. INSTALLATION
    It is recommended that you install all the other RadioLINK Bases / Alarms
    and any other RadioLINK components before installing this MCP.
    All RadioLINK units should be located in their final positions before
    House Coding commences.
    1. The MCP should be positioned (approx) 1.2 meters high on a wall, in
    a suitable location on an exit route (avoid locating near metal objects).
    2. Securely attach the mounting box to the wall using the fixing screws
    supplied.
    3. Remove the bottom housing by first pushing in the forked end of the
    key (with arrow side out) into the two slots (see Figure 1). The bottom
    housing should drop down by about 10mm and expose the yellow
    edge on the top of the white element (with the black spot). Remove
    the key, pull the bottom housing down and then lift it up to remove
    (see Figure 2).
    4. Next remove the white element by lifting the lower edge (see Figure 3).
    5. Connect the built-in battery by sliding the
    battery switch into the “on” position. (see
    Figure 4).
    6. Press the House Code switch until the light
    on the front turns on red (see Figure 4) (The
    unit will now send out a coded alarm signal
    and the red light will flash).
    7. Screw the front plate to the wall box using the
    two machine screws provided (see Figure 5).
    8. Now re-install the white element, yellow
    edge uppermost (see Figure 6). Replace the
    bottom housing by lining up the two notches
    and carefully pushing it flat - this should
    leave it about 10mm below the bottom edge.
    Now slide the bottom housing upwards (see
    Figure 7). This resets the switch. The yellow
    edge on the white element should now be
    hidden (The unit will now send out a coded
    alarm cancel signal). The red light will then
    continue to flash to show it is in House Code
    mode, for the next 15 minutes.
    9. Immediately put all other RadioLINK
    Smoke Alarms and other components into
    House Code mode within 10 minutes.
    10. In House Code mode, the MCP will now
    send a radio message every 5 seconds. All
    RadioLINK Bases and Smoke/Heat Alarms
    within range that are also in House Code
    mode themselves will memorise the House
    Code of the MCP.
    11. Check that the number of amber light
    flashes (for RadioLINK Bases) or blue light
    flashes (for RadioLINK Smoke Alarms)
    corresponds with the number of units in the
    system (e.g. Bases / Alarms plus MCP). For
    example, with 3 RadioLINK Bases and 1
    MCP you should see 4 amber light flashes
    from each Base.
    (Note: the MCP flashing red light does not
    indicate the number of units in the system. It
    just flashes rapidly to show it is in House
    Code mode. The MCP is only an RF
    transmitter and does not receive any RF
    signals).
    12. Remove all the RadioLINK Bases /
    Alarms from House Code mode as
    described in their instruction leaflets.
    13. The MCP will exit the House Code mode
    by itself after approx. 15 minutes without
    further user intervention.
    However, this could result in problems
    with nearby systems if their units are
    being House Coded at the same time. If
    this is the case remove the MCP from its
    mounting box and then from House Code
    mode by pressing and holding the code
    button until the red light comes on (i.e. use
    the same method as to enter House Code
    mode). Release the button and the red
    light will go out, indicating that the MCP
    has exited House Code mode. Re-
    assemble and attach to box as described
    previously.
    Please note that this will cause the MCP
    to send out a coded alarm signal which
    will activate the RadioLINK Bases /
    Alarms that have previously been House
    Coded during the installation procedure.
    3. CHECKING & TESTING THE MCP
    The MCP is an important alarm device and should be tested after
    installation and then weekly (and after prolonged absence) to ensure
    correct operation as follows.
    a) Check that the light on the front flashes green every 40 seconds.
    This indicates it has power.
    b) Press the black spot and the white element will drop down
    exposing the yellow edge to show it is activated. The light will turn red
    and stay on continuously for 3 seconds and then continue to flash red
    (every 20 seconds) for 5 minutes indicating transmission of the alarm
    signal (Note: after 5 minutes the RF alarm signal ceases and
    therefore the smoke alarms will stop alarming. This prevents the
    batteries in the MCP and the alarm from being depleted).
    c) Check the RadioLINK units are now in alarm (If some or all of the
    alarms have not been activated, then the House Coding procedure
    should be repeated. If there are still some problems, see the
    “Troubleshooting RF Link” section on page 4).
    d) The MCP should be reset with the plastic key provided by pushing
    the forked end (arrow side up) into the slots (see Figure 1) and pulling
    the bottom housing down. Remove the plastic key. Now push the
    bottom housing firmly against the back and slide upwards. This resets
    the switch.The yellow strip on the white element should now be hidden.
    e) If the MCP is not reset the light will flash red every 40 seconds to
    remind the user to reset it.
    On reset, the alarm cancel signal will be transmitted (indicated by a
    single red light flash for 3 seconds).
    If the light flashes amber every 9 seconds this indicates that the
    batteries are depleted and the MCP will no longer be able to send an
    alarm signal. The unit must be removed from its location and returned
    for repair if within the guarantee period, (see sections 7 & 8 for details).
    Manual Call Point
    Model: Ei 407
    For use with RadioLINK Smoke/Heat Alarms and Bases
    House Code Button
    BATTERY
    ON/OFF SWITCH
    Figure 1
    Figure 6
    Figure 7
    Figure 3
    Figure 2
    Figure 4
    1
    2 3
    Contains vital information on the product’s operation and installation.
    Read and retain carefully. If you are just installing this product the
    manual MUST be given to the householder.
    Figure 5
    A15268-R2-EI407-UC-ENG 16/8/10 11:28 AM Page 1
Ei Electronics Ei407

¿Necesita ayuda?

Número de preguntas: 0

¿Tiene alguna pregunta sobre Ei Electronics Ei407 o necesita ayuda? Haga su pregunta aquí. Proporcione una descripción clara y completa del problema y su pregunta. Cuantos más detalles proporcione para su problema y pregunta, más fácil será para otros propietarios de Ei Electronics Ei407 responder adecuadamente a su pregunta.

Vea el manual de Ei Electronics Ei407 aquí, de forma gratuita. Este manual pertenece a la categoría Interruptores y ha sido calificado por 1 personas con un promedio de 9.9. Este manual está disponible en los siguientes idiomas: Inglés. ¿Tiene alguna pregunta sobre Ei Electronics Ei407 o necesita ayuda? Haz tu pregunta aquí

Especificaciones de Ei Electronics Ei407

General
Marca Ei Electronics
Modelo Ei407
Producto Interruptor
EAN 5099383004090
Idioma Inglés
Tipo de archivo PDF
Características
Color del producto Rojo
Tecnología de conectividad Inalámbrico
Frecuencia de transmisión RF 868.5MHz
Cantidad de alarmas interconectadas (máx.) 12
Interconectables
Rango de transmisión RF 150m
Material Vidrio
Control de energía
Alimentación Batería
Tecnología de batería Litio
Peso y dimensiones
Peso 191g
Ancho 85mm
Profundidad 58mm
Altura 85mm
Condiciones ambientales
Intervalo de temperatura operativa 0 - 40°C
Intervalo de humedad relativa para funcionamiento 15 - 95%

ManualPDF.es

¿Busca un manual? ManualPDF.es asegura que encontrará el manual que está buscando en un abrir y cerrar de ojos. Nuestra base de datos contiene más de 1 millón de manuales en PDF de más de 10.000 marcas. Cada día añadimos los últimos manuales para que siempre encuentres el producto que buscas. Es muy sencillo: simplemente escriba el nombre de la marca y el tipo de producto en la barra de búsqueda y podrá ver instantáneamente el manual de su elección en línea de forma gratuita.

ManualPDF.es

© Copyright 2020 ManualPDF.es. Todos los derechos reservados.

Utilizamos cookies para asegurar que damos la mejor experiencia al usuario en nuestro sitio web. Si continúa utilizando este sitio asumiremos que está de acuerdo.

Leer más